
7 Proper Cabling in RS 485 and RS 422
The Polarization Resistors must not be too small, because a transmitter has to act against them.
A typical transmitter provides up to 60 mA of current in high and low level.
With the isolated models the polarization option may have additional advantage. As said above
RS 485 requires a connection of GND signals, otherwise the signals at the receiver may be out of
bounds of the Common Voltage Range. Since on SI-models the driver and polarization voltage are
isolated, the received signals are now in the required range. As a result only two wires are required
for data transmission.
Attention: this is the situation if the isolated VScom Industrial Card is the only device with
polarization active.
7.4 2-Wire Scheme
In many configurations a very simple cabling is required. RS 485 allows for so called 2-wire cabling
as shown below. Several devices are connected in parallel to the wires, which is called bus topology.
Each device can either send or receive data at a given time, so it is operating in half-duplex mode.
Shown in figure 26 are three devices, RS 485 specifies up to 32. The data lines are named as Data+
and Data-, a positive differential voltage is the state for a transmitted One. The GND is also
connected between all devices as required
12
.
Figure 26: 2-Wire Cabling Scheme
The resistors P1 and P2 are for polarization, T1 and T2 are for the termination function. Polar-
ization of Data+ and Data- appears only once on this net, the termination is at the physical ends
of the cable.
All devices appear the same on the cable, they have the same function. There is no Master or
Slave defined by the hardware. Such functions are implemented by way of the data transmission
protocol. Also RS 485 addresses are defined by that protocol, as well as bus access.
12
See 7.3 for isolated VScom Industrial Card
July 2011 VScom Industrial Card User Manual 48
Comentarios a estos manuales